Query: UMLS:C0023241 (
Legionella
)
6,990
document(s) hit in 31,850,051 MEDLINE articles (0.00 seconds)
Cooling tower water has frequently been cited as a source of infection in outbreaks of
Legionnaires' disease
. However, there have been few reports on the presence of legionellae in aerosols from cooling towers. This paper describes our use of an impinger or a six-stage microbial impactor for detecting legionellae in air around a cooling tower contaminated with L. pneumophila (1.2+/-0.3x10(5) CFU/100 ml).
Phosphate
-buffered saline, Page's saline, 2% yeast extract solution and buffered yeast extract (BYE) broth were tested to evaluate their collection efficiency. These solutions were compared in laboratory experiments using an aerosol of L. pneumophila serogroup (SG) 1. Because BYE broth was the most efficient and storable collecting fluid among them, it was used for outdoor air sampling. In the outdoor air sampling, aerosolized L. pneumophila SG 6 was detected in the air around the cooling tower by the impinger (0.09 CFU/l. air). No legionellae were detected by the impactor with
Legionella
-selective agar plates (WYOalpha) because the plates were overgrown with fungi. Repetitive element PCR (rep-PCR) and arbitrarily primed PCR (AP-PCR) were employed to assess the epidemiological relationship among
Legionella
isolates from the air sample and the cooling tower water samples. L. pneumophila SG 6 isolated from the aerosols produced rep-PCR and AP-PCR fingerprints identical to those of L. pneumophila SG 6 strains from the cooling tower water, suggesting that the bacterium was aerosolized from the cooling tower.
...
PMID:Sampling and detection of Legionella pneumophila aerosols generated from an industrial cooling tower. 1151 91
Copper is widely used in drinking water premise plumbing system materials. In buildings such as hospitals, large and complicated plumbing networks make it difficult to maintain good water quality. Sustaining safe disinfectant residuals throughout a building to protect against waterborne pathogens such as
Legionella
is particularly challenging since copper and other reactive distribution system materials can exert considerable demands. The objective of this work was to evaluate the impact of pH and orthophosphate on the consumption of free chlorine associated with corroding copper pipes over time. A copper test-loop pilot system was used to control test conditions and systematically meet the study objectives. Chlorine consumption trends attributed to abiotic reactions with copper over time were different for each pH condition tested, and the total amount of chlorine consumed over the test runs increased with increasing pH.
Orthophosphate
eliminated chlorine consumption trends with elapsed time (i.e., chlorine demand was consistent across entire test runs).
Orthophosphate
also greatly reduced the total amount of chlorine consumed over the test runs. Interestingly, the total amount of chlorine consumed and the consumption rate were not pH dependent when orthophosphate was present. The findings reflect the complex and competing reactions at the copper pipe wall including corrosion, oxidation of Cu(I) minerals and ions, and possible oxidation of Cu(II) minerals, and the change in chlorine species all as a function of pH. The work has practical applications for maintaining chlorine residuals in premise plumbing drinking water systems including large buildings such as hospitals.
...
PMID:Impact of water quality on chlorine demand of corroding copper. 2682 46